Desuperheater

From SysCAD Documentation

Jump to: navigation, search

Navigation: Models -> Energy Transfer Models


Contents

General Description

The Desuperheater is designed to cool superheated steam by the addition of a water stream.

This unit can be used as part of a Flash Train, where a Desuperheater is in a steam line between a steam source and steam sink (eg shell & tube heater). By adding water, the 'superheating' in the steam can be used to increase the steam volume flowrate while maintaining a similar temperature.

The best way to operate the de-superheater is to have the water stream in Demand mode. However, the user can also use it in the general mode so that constant water feed is supplied. Note: in this case, the outlet steam temperature may not be met. These 2 modes are described below:

Water in Demand mode

This is where the water feeder connected to the Desuperheater is set to Demand mode, as shown below:

Image:Feeder_Demand.jpg

When the Feeder is set up in Demand mode, the amount of water needed by the unit to achieve the required temperature is transferred to the connecting water line and delivered to the Desuperheater by the feeder.

Notes:

  • The Feeder Mode can be either Source_ConstQm or Source_ConstQv
  • Demand.On MUST be enabled
  • If the value specified in the 'Qm_Rqd (Min) field is larger than the calculated water requirement, the water fed to the Desuperheater will be in excess.
  • The demand logic often works better if the Qm_Rqd (Min) field is a small number rather than zero.

General calculation mode

This is where the water connection to the Desuperheater is NOT in Demand mode. PGM code or a PID unit may be required to set the water flowrate to achieve the required temperature.

Note: The Desuperheater unit does display the amount of water required to achieve the desuperheating requirements, and this can be used to adjust the water flow to the unit.

Diagram

Image:Models-Desuperheater-image001.gif

The diagram shows the default drawing of the Desuperheater, with the required connecting streams. The unit will not operate unless all of the above streams are connected.

The physical location of the connections is not important; the user may connect the streams to any position on the drawing.

Inputs and Outputs

LabelInput /OutputNo. of ConnectionsDescription
MinMax
SteamIn In 1 1 The Superheated Steam feed.
SteamOut Out 1 1 The Desuperheated Steam Outlet.
FeedLiq In 1 1 The spray water stream.

Model Theory

  • The unit pressure is equal to the pressure of the incoming superheated steam.
  • The Desuperheater attempts to achieve steam:water equilibrium at the unit pressure. In normal operation this will involve flashing all of the spray water to achieve the user defined conditions.
  • The temperature and amount of material which changes phase is calculated using an adiabatic flash routine. Please see Vapour Liquid Equilibrium (VLE) for more information.
  • The Temperature : Pressure curves for saturated steam is part of the SysCAD internal data. The equilibrium point will be that of saturated steam, as found in Steam Tables.

The user can specify the amount of superheat to be removed in the following ways:

  1. Temperature Drop. The maximum temperature drop allowed by the model is the difference between the amount of superheat of the incoming steam and the saturated temperature at the total unit pressure. If the user required temperature drop is greater than this value, the final temperature will be the saturated temperature and the unit will flag an error.
  2. Final Temperature. The maximum temperature allowed is the incoming steam temperature and the minimum temperature allowed by the model is the saturated temperature at the total unit pressure. If the user required final temperature is outside of this range, the unit will flag an error.
  3. Approach to Saturation Temperature. The user specifies the degrees above saturation of the exiting steam. The maximum approach allowed is the degrees of superheat of the incoming steam. If the user required approach is greater than this value, the unit will flag an error. The minimum approach allowed is zero.
  4. Saturated. The exiting steam is required to be at the saturated values at the unit pressure.

Assumptions and Limitations

  1. The Desuperheater is a constant enthalpy, constant pressure process.
  2. The Steam line into the unit contains SUPERHEATED steam.
  3. The Liquid line into the unit contains water.
  4. When the water is in Demand Mode, the minimum outlet steam temperature will be limited to its saturation temperature.
  5. When the water is not in Demand mode, the outlet steam temperature can be reduced to below its saturation Temperature if too much spray water is added. When this happens, the steam outlet will not be in the correct state. Therefore, the spray water should be in Demand mode wherever possible. If this is not possible, use a PGM to get the correct required water flowrate (FlowRqd - calculated by SysCAD based on the required temperature change) and use it to set the water flow.

Data Sections

The default sections and variable names are described in detail in the following tables. The default Desuperheater access window consists of 3 sections. This number may increase or decrease, based on user configuration.

  1. The first section, which has the same name DesuperHeater, contains general information relating to the unit
  2. The Info section, contains general settings for the unit and allows the user to include documentation about the unit and create Hyperlinks to external documents. This is fully described in Common Data Sections.
  3. Links tab, only visible in SysCAD 9.2, contains a summary table for all the input and output streams.
  4. Audit tab - contains summary information required for Mass and Energy balance. See Model Examples for enthalpy calculation Examples.

Class: DesuperHeater - The first tab page in the access window will have this name.

Tag / Symbol

Input / Calc

Description/Calculated Variables / Options

Common First Data Section

Requirements

TempSpec Temp Drop The user specifies the required temperature drop in the steam line.

Note: If the required temperature drop means that the final steam temperature would be below the saturated temperature, then a warning will be given and the final temperature will be restricted to the saturated temperature at the unit total pressure.

Final Temp The user specifies the required temperature of the outlet steam.

Note: If the required final temperature is above the inlet steam temperature or below the saturated temperature, then a warning will be given and the final temperature will be restricted to either the saturated temperature at the unit total pressure or the inlet steam temperature.

Approach SatT The user can specify the approach temperature to saturation. Thus, if Approach SatT is 5, then Steam Exit Temperature = Saturation Temperature at total unit Pressure + 5.

Note: If the required approach is greater than the degrees of superheat of the inlet steam, then a warning will be given and the final temperature will be restricted to the inlet steam temperature.

Saturated The exit steam will be at the saturation temperature at the total unit pressure. This is equivalent to an Approach of 0.
TDropRqd Input This field is only visible if the user selects Temp Drop for the TempSpec. The required temperature drop across the steam line.
FinalTRqd Input This field is only visible if the user selects Final Temp for the TempSpec. The final steam temperature required.
ApproachSatT Input This field is only visible if the user selects Approach SatT for the TempSpec. The approach temperature to the steam saturated temperature.
Strict Tick Box If this is enabled, then the user will receive a warning if the user required conditions are NOT achieved.

Options

ShowQFeed Tick Box QFeed and associated tab pages (eg Qm) will become visible, showing the properties of the combined feed stream. See Material Flow Section. This will be prior to any flashing occurring.
ShowQProd Tick Box QProd and associated tab pages (eg Qm) will become visible, showing the properties of the product stream. See Material Flow Section. This will be after any flashing occurs.
TrackPureSteam TickBox This adds a check for the composition of the Steam feed. If the line does NOT contain 100% steam a warning will be generated - Expect pure steam in steam feed.
TrackPureWater TickBox This adds a check for the composition of the FeedLiq stream. If the line does NOT contain 100% water a warning will be generated - Expect pure water in feed liquor feed.

Results

Cooling water addition
FlowRqd Calc This is the required spray water flow calculated by SysCAD to achieve the specified outlet temperature.
ActualFlow Calc This is the Actual spray water flow entering the unit operation.
FlowRqdForSatT Calc This is the amount of spray water that is required to produce saturated steam at the total unit pressure.
Steam inlet
Steam.Ti Display This is the temperature of the steam entering the unit.
Steam.SatTi Calc The Saturation Temperature of the Steam entering the unit.
Steam.DegSuperHeat Calc The degree of superheat of the steam entering the unit. (The saturation temperature is calculated at the total unit pressure = steam feed pressure).
Steam.Pi Display The pressure of the feed steam.
Steam.Vfi Display The steam fraction in the feed steam (normally 100%).
Steam.InFlashed Tickbox This will be enabled if the steam entering the unit contains any liquid water to indicate to the user that the water has been flashed.
FlashSteam.Ti Display This is the temperature of the steam after it has been automatically flashed. If there is no water in the feed stream, this will be the same as the temperature of the steam entering the unit.
FlashSteam.DegSuperHeat Calc The degree of superheat of the steam after it has been automatically flashed. If there is no water in the feed stream, this will be the same as the degree of superheat of the steam entering the unit.
Steam outlet
TDrop Calc The temperature drop of the steam across the unit.
To Calc This is the temperature of the steam leaving the unit.
SatT Calc The Saturation Temperature of the steam leaving the unit.
DegSuperHeat Calc This is the degree of superheat the steam outlet contains.
Po Display The pressure of the steam leaving the unit.
Vfo Calc The vapour fraction in the stream leaving the unit.

Adding this Model to a Project

Insert into Configuration file

Sort either by DLL or Group.

 

DLL:

HeatXch1.dll

Units/Links

Heat Transfer: Desuperheater

or

Group:

Energy Transfer

Units/Links

Heat Transfer: Desuperheater

See Project Configuration for more information on adding models to the configuration file.


Insert into Project

 

Insert Unit

Heat Transfer

Desuperheater

See Insert Unit for general information on inserting units.

Hints and Comments

  1. Refer to Assumptions and limitations under Model Theory.